Analisa Pengaruh Arus Bocor Terhadap Total Harmonic Distortion Pada Isolator 150 kV Yang Terkontaminan Lumut Menggunakan Transformasi Fourier

Authors

  • Rachmat Deska Saputra Institut Teknologi Padang, Indonesia
  • Sitti Amalia Institut Teknologi Padang, Indonesia
  • Yusreni Warmi Institut Teknologi Padang, Indonesia
  • Sepannur Bandri Institut Teknologi Padang, Indonesia
  • Andi M Nur Putra Institut Teknologi Padang, Indonesia

DOI:

https://doi.org/10.70609/gtech.v8i4.5476

Keywords:

Leakage Current, FFT, Insulator, NI DIAdem, THD

Abstract

This study investigates the Total Harmonic Distortion (THD) of 150 kV insulators contaminated with moss based on leakage current patterns with three variations of test voltages, namely 10,578 V, 21,063 V, dan 30,569 V. The tests were conducted experimentally at the High Voltage Laboratory of Gajah Mada University with a temperature of 28.2 °C dan humidity of 57.8%. The test was conducted experimentally at the High Voltage Laboratory of Gajah Mada University with a temperature of 28.2°C dan humidity of 57.8%. The analyzed parameters include waveform, frequency spectrum (FFT), dan THD, which were calculated using Fast Fourier Transform (FFT) through NI DIAdem software. The test results showed no strong relationship between leakage current dan THD. At a leakage current of 0.103 mA, the resulting THD is 21.84%, while at a current of 0.207 mA produces a THD of 18.27%, dan 0.306 mA produces a THD of 36%. Based on the IEEE STD 519-2014 stdanard, THD on 150 kV insulators contaminated with moss exceeds the maximum limit of 15%, so this insulator is not safe to use on the Koto Panjang-Payakumbuh transmission line.

References

Adam, Febrian. 2023. Analisa Total Harmonic Distortion Pada Sistem Tenaga Listrik Menggunakan Aliran Daya Harmonik.

Alfina, Riny, Indrawan Arifianto, Dwi Astharini, dan Putri Wuldanari. 2019. “Mendisain GUI Untuk Menampilkan Nilai FFT Dan IFFT Menggunakan LabVIEW.” TESLA: Jurnal Teknik Elektro 21(1):50. doi: 10.24912/tesla.v21i1.3250.

Azzahra, Magvira Apriliana. 2022. “Investigasi Eksperimental Kekuatan Dielektrik Isolator Pada Saluran Transmisi 150 KV Koto Panjang – Payakumbuh.” Prosiding Sains Nasional Dan Teknologi 12(1):539. doi: 10.36499/psnst.v12i1.7205.

Dimitropoulou, M., D. Pylarinos, K. Siderakis, E. Thalassinakis, dan M. Danikas. 2015. “Comparative Investigation of Pollution Accumulation dan Natural Cleaning for Different HV Insulators.” Engineering, Technology & Applied Science Research 5(2):764–74. doi: 10.48084/etasr.545.

Fauzan, Muhamad, Fitri Rahma Yanti, Magvira Apriliana Azzahra, Affalenza Ahmad, dan Yusreni Warmi. 2022. “Investigasi Flashover Pada Saluran Transmisi 150 KV Payakumbuh – Koto Panjang.” Sinarint 177–84.

Halomoan, Ravento Viko. 2017. “MENGGUNAKAN TEGANGAN IMPULS Ravento Viko Halomoan Skripsi Ini Ditulis Untuk Memenuhi Sebagian Persyaratan Dalam Memperoleh Gelar Sarjana Pendidikan PROGRAM STUDI PENDIDIKAN TEKNIK ELEKTRO.”

Heri, Johanadib, dan Abdul Syakur. 2012. “Studi Arus Bocor Permukaan Bahan Isolasi Resin Epoksi Silane Dengan Variasi Pengisi Pasir Silika (Dengan Polutan Pantai).” Transmisi 14(1):20-37–37.

Jumari, Joslen Sinaga, dan Sudirman Zega. 2020. “STUDI PENGARUH KONTAMINASI POLUSI UDARA PADA ISOLATOR TEGANGAN MENENGAH 20 KV PADA PT PLN (Persero) UNIT PELAKSANA PELAYANAN PELANGGAN (UP3) MEDAN.” Jurnal Teknik Elektro 9(1):31–43.

Koerniawan, Tony, dan Aas Wasri Hasanah. 2019. “Kajian Harmonisa Pada Pemakaian Tenaga Listrik Gedung STT-PLN Jakarta.” Kilat 8(2):180–89. doi: 10.33322/kilat.v8i2.547.

Luntungan, Renaldi P., Lily S. Patras, dan Glanny MCh Mangindaan. 2018. “Analisa Daerah Lindung Dan Grounding Pada Tower Transmisi Akibat Terjadinya Back Flashover.” Journal Teknik Elektro Dan Komputer 7(3):199–206.

Muhammad Suyanto. 2014. “Pengujian Isolator Pin-Post 20KV Terkontaminasi Garam Mengakibatkan Arus Bocor Flashover Pada Permukaan Isolator.” Snast (November):211–16.

Rajagukguk, Managam. 2011. “Analisis Karakteristik Flashover Dan Arus Bocor Pada Isolator Porselin Yang Dipengaruhi Polutan Lumut Bryum SP.” Jurnal ELKHA 3(2):35–38.

Samosir, A. S. 2015. “Analisis Dan Visualisasi Representasi Deret Fourier Gelombang Sinyal Periodik Menggunakan MATLAB.” Electrician: Jurnal Rekayasa Dan Teknologi … 9(3).

Setiawan, Awan, Imron Ridzki, dan Priya Surya. 2020. “Pengaruh Tegangan Kerja Terhadap Spektrum Frekuensi Gelombang Arus Bocor Pada Isolator Keramik.” Jurnal Eltek 18(2):59. doi: 10.33795/eltek.v18i2.255.

Trewin, Dennis. 2006. “Diadem Basic.” Business 1(325290):1–20.

Warmi, Yusreni. 2019. “Analisa Pengaruh Panjang Gap Arcing Horn Terhadap Jumlah Trip-out Pada Saluran Transmisi 150 KV Payakumbuh – Koto Panjang.” Jurnal Teknik Elektro ITP 8(2):82–86. doi: 10.21063/jte.2019.3133815.

WARMI, YUSRENI, dan KAZNI FEBRIAN. 2021. “Analisis Variasi Ketebalan Coating Senyawa Glasir Terhadap Daya Tahan Dielektrik Isolator Keramik Saluran Transmisi 150kV.” ELKOMIKA: Jurnal Teknik Energi Elektrik, Teknik Telekomunikasi, & Teknik Elektronika 9(2):249. doi: 10.26760/elkomika.v9i2.249.

Warmi, Yusreni, dan Koji Michishita. 2016. “Investigation of Lightning Tripouts on 150-KV Transmission Lines in West Sumatra in Indonesia.” IEEJ Transactions on Electrical dan Electronic Engineering 11(5):671–73. doi: 10.1002/tee.22286.

Warmi, Yusreni, dan Koji Michishita. 2018. “Tower-Footing Resistance dan Lightning Trip-Outs of 150 KV Transmission Lines in West Sumatra in Indonesia.” MATEC Web of Conferences 215:4–11. doi: 10.1051/matecconf/201821501022.

Yanti, Fitri Rahma. 2022. “Analisa Pengaruh Kontaminan Isolator Terhadap Jumlah Flashover Pada Saluran Transmisi 150 KV Koto Panjang-Payakumbuh.” Prosiding Sains Nasional Dan Teknologi 12(1):559. doi: 10.36499/psnst.v12i1.7212.

Published

2024-10-29

How to Cite

Analisa Pengaruh Arus Bocor Terhadap Total Harmonic Distortion Pada Isolator 150 kV Yang Terkontaminan Lumut Menggunakan Transformasi Fourier. (2024). G-Tech: Jurnal Teknologi Terapan, 8(4), 2938-2945. https://doi.org/10.70609/gtech.v8i4.5476

Most read articles by the same author(s)